Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number 8
REA-NEP-MG EEP3
Register as Individual
NEMSA Certificate Number AO1372
First Name Oluseyi
Last Name Odubanjo
Position Senior Electrical Engineer
Phone 08035384537
Email odubanjooluseyi@gmail.com
Address

sAbeokuta, ogun

State Ogun
Name of the Village/Community Federal University of Technology Akure
State Ondo
Local Government Area Akoko North-West
Number of Inhabitants 800
GPS Coordinates 7°18’25.36″N, 5° 7’51.33″E
Site Address/Detail Description

Federal University of Technology Akure

Activities Educational Facility
Total Solar PV Installed (kWp) 4514
Total Solar PV Energy Produce Per Day (kwh) 19600
Total Storage Capacity (kwh) 5504
Total Load/Energy Requirement (kWh) 14580
Storage Technology/Manufacturer SUNGROW
Type of Coupling (AC/DC) AC
Generator Rated Power (kVA) 2600
Year of Construction 2025
Fuel Type Diesel
Generator Model/Manufacturer Sterling and Wilson/P650
Operation Automatic
Date of Installation of Mini-Grid October 7, 2025
Date of Application November 4, 2025
Mini-Grid Owner (Full Name) REA
Email odubanjooluseyi@gmail.com

Manufacturer ZNSHINE SOLAR
Model ZXM8-TP132/660
Technology Monocrystalline PERC
STC power (Wp) 660
Number of Cells 132
MPPT Current 17.47
MPPT Voltage 37.8

Module catalogue # ZXM8-TP132/660
Number Series | Parallel 30/228
Total Power (Wp) 19800
Fuse (A) 30
Surge Protection Device SPD TYPE I+II
Converter Catalogue Sungrow
Cable cross-section 4mm2

Manufacturer SUNGROW
Model SG350HX
Technology String Inverter
Rated Power 350KW
Rated Voltage 800VAC
Rated Current 254

Manufacturer SUNGROW
Model LFP
Technology LFP
Cell Voltage (V) 3.2
Battery Voltage 204
C10 Capacity 280Ah
Charge Voltage 233

Module Catalogue # R344-111
Number Series | Parallel 64/1
Total C10 capacity [kWh] 2752
Fuse rating [A] 420
Date of cell production September 6, 2024
Date of installation May 9, 2025
Cable cross-section [mm²] 240

PV Generator String cables fixed and cables without damages
String Number 1
Value 1

Inverter/Charge Controller General visual inspection observations
String Number 2
Reference 1

Battery Storage General visual inspection observations
String Number 3
Reference 1

General Safety/Security General visual inspection observations
String Number 4
Reference 1
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Request-Letter-LOT8-ICC-SUNGROW.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Solar-Panel-Datasheet-1-1.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/DS_20231208_SG350HX_Datasheet_V20_EN-2.pdf
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/DS_20220222_SC1200_1375_1575_1725UD_Datasheet_V15_EN-1.pdf
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/DS_20230509_ST2752UX_Datasheet_V16_EN-1.pdf
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/EL-Schematic-Detail-Lot8.pdf
User ID Jad Zeineddine