Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number 3
REA-NEP-MG EEP3
Register as Individual
NEMSA Certificate Number AO1372
First Name Oluseyi
Last Name Odubanjo
Position Senior Electrical Engineer
Phone 08035384537
Email odubanjooluseyi@gmail.com
Address

sAbeokuta, ogun

State Federal Capital Territory
Name of the Village/Community Federal University of Lafia
State Nasarawa
Local Government Area Lafia
Number of Inhabitants 300
GPS Coordinates 8.479254745264706, 8.560467374498657
Site Address/Detail Description

Federal University of Lafia

Activities Educational Facility
Total Solar PV Installed (kWp) 1647
Total Solar PV Energy Produce Per Day (kwh) 8101
Total Storage Capacity (kwh) 4301
Total Load/Energy Requirement (kWh) 10215
Storage Technology/Manufacturer ZNSHINE PV TECH
Type of Coupling (AC/DC) AC
Generator Rated Power (kVA) 1000
Year of Construction 2025
Fuel Type Diesel
Generator Model/Manufacturer Sterling and Wilson/P500
Operation Automatic
Date of Installation of Mini-Grid August 1, 2025
Date of Application September 9, 2025
Mini-Grid Owner (Full Name) REA

Manufacturer ZNSHINE SOLAR
Model ZXM7-SHLD144/550
Technology Double Glass Monocrystalline PERC PV Module
STC power (Wp) 550
Number of Cells 144
MPPT Current 13.16
MPPT Voltage 41.8

Module catalogue # ZXM7-SHLD144/550
Number Series | Parallel 28/107
Total Power (Wp) 15400
Fuse (A) 25
Surge Protection Device SPD TYPE I+II
Converter Catalogue Sungrow
Cable cross-section 4mm2

Manufacturer SUNGROW
Model SG350HX
Technology String Inverter
Rated Power 350KVA
Rated Voltage 800VAC
Rated Current 254A

Manufacturer SUNGROW
Model LFP
Technology LFP
Cell Voltage (V) 3.2
Battery Voltage 204
C10 Capacity 280Ah
Charge Voltage 233

Module Catalogue # R344-111
Number Series | Parallel 64/1
Total C10 capacity [kWh] 286.72
Fuse rating [A] 420
Date of cell production September 6, 2024
Date of installation May 9, 2025
Cable cross-section [mm²] 240

PV Generator String cables fixed and cables without damages
String Number 1
Value 1

Inverter/Charge Controller General visual inspection observations
String Number 2
Reference 1

Battery Storage General visual inspection observations
String Number 3
Reference 1

General Safety/Security General visual inspection observations
String Number 4
Reference 1
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Request-Letter-LOT3-ICC-SUNGROW.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Solar-Panel-Datasheet.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/DS_20220222_SC1200_1375_1575_1725UD_Datasheet_V15_EN.pdf
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/DS_20231208_SG350HX_Datasheet_V20_EN-1.pdf
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/DS_20230509_ST2752UX_Datasheet_V16_EN.pdf
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Lot3.-Solar-Plant-Site-Layout09-09-25-EARTHING-and-LPS.pdf
User ID Jad Zeineddine