Admin Request for Inspection REA Solar Mini Grid
| Application for | REA Solar Mini-Grid Project |
|---|---|
| REA Code | REA-NEP-MG |
| REA LOT Number | N/A |
| REA-NEP-MG | PBG |
| Register as | Corporate |
| NEMSA Certificate Number | CC/CEIF/PR/04431 |
| First Name | Akposio |
| Last Name | Ogaga |
| Position | Senior Site Lead |
| Phone | 08033770950 |
| akposio_ogaga_ng@huskpowersystems.com | |
| Address |
Galadimawa, Abuja |
| State | Federal Capital Territory |
| Company Name | Husk Power Energy Systems |
| Company Email | info@huskpowersystems.com |
| Company Phone | 08097814273 |
| Tax Registration Number | 6500209934 |
| Address |
Plot 25, Ndola Crescent, Wuse Zone 5, Abuja |
| State | Federal Capital Territory |
| Name of the Village/Community | Ajuye |
| State | Nasarawa |
| Local Government Area | Kokona |
| Number of Inhabitants | 2000 |
| GPS Coordinates | 8.94183923 8.01309073 |
| Site Address/Detail Description |
Ajuye Community, Kokona Local Government Area, Via Keffi-Akwanga Road, Nasarawa state. |
| Activities | Business Activity, Administrative Facility, Educational Facility, Health Care Facility, Residential |
| Total Solar PV Installed (kWp) | 50 |
| Total Solar PV Energy Produce Per Day (kwh) | 2971 |
| Total Storage Capacity (kwh) | 244.8 |
| Total Load/Energy Requirement (kWh) | 1700 |
| Storage Technology/Manufacturer | VRLA/ Amara Raja |
| Type of Coupling (AC/DC) | DC |
| Generator Rated Power (kVA) | 30 |
| Year of Construction | 2024 |
| Fuel Type | Diesel |
| Generator Model/Manufacturer | 3445 TCIGM-C2 Powerol by Mahindra |
| Operation | Manual |
| Date of Installation of Mini-Grid | November 6, 2024 |
| Date of Application | June 28, 2025 |
| Mini-Grid Owner (Full Name) | Husk Power Systems |
| Phone | 08097814273 |
| info@huskpowersystems.com | |
| Manufacturer | JA Solar |
| Model | JAM72D40-565/MB |
| Technology | Bifacial Double Glass High Efficiency Low LID Mono PERC with Half Cut Technology |
| STC power (Wp) | 565 |
| Number of Cells | 144 |
| MPPT Current | 13.32 |
| MPPT Voltage | 42.42 |
| Module catalogue # | JAM72S30-545/MR |
| Number Series | Parallel | 12/2 |
| Total Power (Wp) | 13200 |
| Fuse (A) | 20 |
| Surge Protection Device | 1000 VDC 20 kA |
| Converter Catalogue | N/A |
| Cable cross-section | 6mm (PV to combiner box) |
| Manufacturer | Statcon Energia |
| Model | HBD-240-050K-3P-030M2-11-CO1 |
| Technology | Smart Storage Inverter |
| Rated Power | 50 kW |
| Rated Voltage | 240 VAC |
| Rated Current | 72.2 A |
| Manufacturer | Amara Raja |
| Model | IP1X21 |
| Technology | VRLA |
| Cell Voltage (V) | 2 V |
| Battery Voltage | 240 |
| C10 Capacity | 1020 |
| Charge Voltage | 265 |
| Module Catalogue # | High Performance VRLA |
| Number Series | Parallel | 120/0 |
| Total C10 capacity [kWh] | 180 |
| Fuse rating [A] | 160 |
| Date of cell production | March 16, 2024 |
| Date of installation | November 1, 2024 |
| Cable cross-section [mm²] | 95 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 1 |
| Value | 613 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 2 |
| Value | 613 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 3 |
| Value | 613 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 4 |
| Value | 613 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 5 |
| Value | 613 |
| Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
| String Number | 1 |
| Reference | Yes |
| Battery Storage | General visual inspection observations |
| String Number | 1 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 2 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 3 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 4 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 5 |
| Reference | Good |
| General Safety/Security | General visual inspection observations |
| String Number | 1 |
| Reference | SPD, FUSES, & BREAKERS ‘OK’ |
| Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/NEMSA-5.pdf |
| PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/6b84e-jam72d40-565-590-mb-global_en_20230926a.pdf |
| Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/DATA-SHEET-FOR-HBD-240V-50KW-NIGERIA-7-3.pdf |
| Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/AJB-3-INPUT-7-2.pdf |
| Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/240V-1020Ah-Drawing-Export-1.pdf |
| Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/HMG-NG-EL-V2-23-01-Earthing-1-7-3.pdf |
| User ID | Akposio Ogaga |