Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number Null
REA-NEP-MG PBG
Register as Corporate
NEMSA Certificate Number RECC/CEIF/PR/00254
First Name ZHENGQUAN
Last Name ZHOU
Other Name JOEY
Position MANAGING DIRECTOR
Phone 08037259175
Email zhouzq@startimes.com.cn
Address

1124 Eldoret Close, Aminu Kano Crescent, Wuse 2, Abuja

State Federal Capital Territory
Company Name STARTIMES SMART ENERGY NIG LTD
Company Email zhouzq@startimes.com.cn
Company Phone 08037259175
Tax Registration Number 1258044
Address

11/12 FATAI ATERE WAY MUSHIN, LAGOS

State Lagos
Name of the Village/Community Jos south
State Plateau
Local Government Area Jos South
Number of Inhabitants 15
GPS Coordinates 9°47’59.20″N, 8°54’53.95″E
Site Address/Detail Description

St. Augustines College Du Shen, Jos

Activities Educational Facility
Total Solar PV Installed (kWp) 13.2
Total Solar PV Energy Produce Per Day (kwh) 59.4
Total Storage Capacity (kwh) 20
Total Load/Energy Requirement (kWh) 15
Storage Technology/Manufacturer Startimes
Type of Coupling (AC/DC) DC
Generator Rated Power (kVA) 40
Year of Construction 2005
Fuel Type Diesel
Generator Model/Manufacturer XP40P1/Marapco
Operation Manual
Date of Installation of Mini-Grid October 12, 2024
Date of Application December 27, 2024
Mini-Grid Owner (Full Name) Re. Father
Phone 08066269635

Manufacturer Startimes
Model CE-550HM
Technology STARTIMES SOLAR
STC power (Wp) 550
Number of Cells 24
MPPT Current 13.32
MPPT Voltage 49.8

Module catalogue # 4
Number Series | Parallel 6S, 1P
Total Power (Wp) 13200
Fuse (A) 32
Surge Protection Device CHiNT
Converter Catalogue 4
Cable cross-section 50

Manufacturer Startimes
Model H50
Technology Startimes
Rated Power 5kva
Rated Voltage 48VDC
Rated Current 100

Manufacturer Startimes
Model H50-B-Xs
Technology LITHIUM
Cell Voltage (V) 3.2VDC
Battery Voltage 51.2V
C10 Capacity 5120wh
Charge Voltage 54VDC

Module Catalogue # 4
Number Series | Parallel 16S,1P
Total C10 capacity [kWh] 5.12
Fuse rating [A] 60
Date of cell production June 17, 2024
Date of installation October 12, 2024
Cable cross-section [mm²] 35

PV Generator Expected open circuit voltage [V]
String Number 1
Value 270.1
PV Generator Expected open circuit voltage [V]
String Number 2
Value 270.2
PV Generator Expected open circuit voltage [V]
String Number 3
Value 270.0
PV Generator Expected open circuit voltage [V]
String Number 4
Value 270.1

Inverter/Charge Controller General visual inspection observations
String Number 1
Reference Normal

Battery Storage General visual inspection observations
String Number 1
Reference Normal

General Safety/Security General visual inspection observations
String Number 1
Reference Normal
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Request-Inspection-Letter-3.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/PV-system-1-150×150.jpg
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/Invertor-1-150×150.jpg
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/Combiner-box-4-150×150.jpg
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/battery-2-150×150.jpg
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/surge-protect-150×150.png
User ID ZHENGQUAN ZHOU