Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number LOT3
Register as Individual
NEMSA Certificate Number CC/CCIF/PR/02615
First Name Olushola
Last Name daley
Position Lead Engineer
Phone 08023036794
Email ipgruppengineering@gmail.com
Address

Plot 204 bwari Rd FCT-Abuja

State Federal Capital Territory
Name of the Village/Community University of Calaba
State Cross Rivers
Local Government Area Calabar Municipal
Number of Inhabitants 48894
GPS Coordinates 4.939889N, 8.346564E
Site Address/Detail Description

Solar Power Plant Site, University of Calaba, Mary Slessor Ave, Calabar 540281, Cross River,Nigeria

Activities Educational Facility
Total Solar PV Installed (kWp) 8003
Total Solar PV Energy Produce Per Day (kwh) 32021
Total Storage Capacity (kwh) 4000
Total Load/Energy Requirement (kWh) 23684
Storage Technology/Manufacturer LFP/Huawei
Type of Coupling (AC/DC) AC
Generator Rated Power (kVA) 4500
Year of Construction 2024
Fuel Type Diesel
Generator Model/Manufacturer HSW-660 T5 / HIMOINSA
Operation Automatic
Date of Installation of Mini-Grid October 15, 2024
Date of Application October 29, 2024
Mini-Grid Owner (Full Name) University of Calaba
Applicant Olushola Daley
Phone 08023036794
Email ipgruppengineering@gmail.com

Manufacturer Ja Solar
Model JAM72S30-555/GR
Technology MONOCRYSTALLINE HALF-CELL
STC power (Wp) 555
Number of Cells 144(6×24)
MPPT Current 13.18
MPPT Voltage 42.11

Module catalogue # JAM72S30
Number Series | Parallel 28S
Total Power (Wp) 15540
Fuse (A) 25
Surge Protection Device NA
Converter Catalogue NA
Cable cross-section 4MMSQ

Manufacturer HUAWEI
Model SUN2000-200KTL-H2
Technology SMART STRING INVERTER
Rated Power 200KW
Rated Voltage 1500
Rated Current 144.4

Manufacturer OEM – EVE POWER COMPANY
Model LF280K
Technology Lithium Iron Phosphate
Cell Voltage (V) 3.2
Battery Voltage 57.6
C10 Capacity 16.13Kwh @ C1
Charge Voltage 65.7

Module Catalogue # JAM72S30
Number Series | Parallel 378S/6p
Total C10 capacity [kWh] 2032
Fuse rating [A] 275.2
Date of cell production October 5, 2023
Date of installation January 15, 2024
Cable cross-section [mm²] 150mm

PV Generator Expected open circuit voltage [V]
String Number 1
Value OK

Inverter/Charge Controller General visual inspection observations
String Number 1
Reference Labelling

Battery Storage General visual inspection observations
String Number 1
Reference Labelling

General Safety/Security General visual inspection observations
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Site-Visit-request-to-NEMSA.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/EEP2-UNICAL-EDD-CDI-001-PV-Inverter-Technical-Datasheets-V2.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/EEP2-UNICAL-EDD-CDI-001-PV-Inverter-Technical-Datasheets-V2-1.pdf
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/DCBOX-DC-LV-Panel-User-Manual.pdf
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/EEP2-UNICAL-EDD-CDB-010-LITHIUM-ION-BATTERIES-TECHNICAL-DATASHEETS-V1-.pdf, https://nemsa.gov.ng/wp-content/uploads/formidable/67/EEP2-UNICAL-E-LAY-EL-003-EARTHING-LAYOUT-LA-LAYOUT-V1-.pdf
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/EEP2-UNICAL-E-DWG-LP-012-LIGHTNING-PROTECTION-SYSTEM-V2-.pdf
User ID shola daley