Admin Request for Inspection REA Solar Mini Grid
Application for | REA Solar Mini-Grid Project |
---|---|
REA Code | REA-NEP-MG |
REA LOT Number | Lot 1 |
REA-NEP-MG | EEP2 |
Register as | Corporate |
NEMSA Certificate Number | CC/CEIF/PR/00231 |
First Name | Odinakachukwu |
Last Name | Agubata |
Position | Project Engineer |
Phone | +2348135175681 |
odinaka@emone.energy | |
Address |
No 21 Danube Street Maitama |
State | Federal Capital Territory |
Company Name | Emone Energy Solutions |
Company Email | info@emone.energy |
Company Phone | +234092912738 |
Tax Registration Number | 17846275-0001 |
Address |
21 Danube Street Maitama |
State | Federal Capital Territory |
Name of the Village/Community | University of Abuja Permanent Site |
State | Federal Capital Territory |
Local Government Area | Gwagwalada |
Number of Inhabitants | 40000 |
GPS Coordinates | Latitude 8.992553, Longitude 7.171086 |
Site Address/Detail Description |
University of Abuja Permanent Site, Airport Road, FCT |
Activities | Educational Facility, Residential |
Total Solar PV Installed (kWp) | 3341.8 |
Total Solar PV Energy Produce Per Day (kwh) | 12848 |
Total Storage Capacity (kwh) | 2032 |
Total Load/Energy Requirement (kWh) | 4549360 |
Storage Technology/Manufacturer | Huawei |
Type of Coupling (AC/DC) | AC |
Generator Rated Power (kVA) | 3400 |
Year of Construction | 2024 |
Fuel Type | Diesel |
Generator Model/Manufacturer | Mikano |
Operation | Automatic |
Date of Installation of Mini-Grid | October 9, 2024 |
Date of Application | October 9, 2024 |
Mini-Grid Owner (Full Name) | Emone Energy Solutions |
Phone | +234092912738 |
info@emone.energy | |
Applicant | Odinakachukwu Agubata |
Phone | +2348135175681 |
odinaka@emone.energy | |
Manufacturer | Canadian Solar |
Model | CS6W-550MS-1500V |
Technology | Monocrystalline |
STC power (Wp) | 550 |
Number of Cells | 144 |
MPPT Current | 30 |
MPPT Voltage | 1500 |
Module catalogue # | CS6W-550MS 1500V |
Number Series | Parallel | 217 |
Total Power (Wp) | 3341800 |
Fuse (A) | 0 |
Surge Protection Device | Type I + II |
Converter Catalogue | CS6W-550MS 1500V |
Cable cross-section | 1C 4mm Cu Cable |
Manufacturer | Huawei |
Model | SUN2000-200kTL-H2 |
Technology | Transformerless |
Rated Power | 215kVA |
Rated Voltage | 800 |
Rated Current | 144.4 |
Manufacturer | Huawei |
Model | LUNA2000-2.0MWH-1H0 |
Technology | Lithium Ion Phosphate |
Cell Voltage (V) | 51.2 |
Battery Voltage | 1250 |
C10 Capacity | 2032kWh |
Charge Voltage | 1020V – 1365V |
Module Catalogue # | Huawei |
Number Series | Parallel | 1 |
Total C10 capacity [kWh] | 2032 |
Fuse rating [A] | 0 |
Date of cell production | December 10, 2022 |
Date of installation | February 10, 2024 |
Cable cross-section [mm²] | 2 x 240 |
PV Generator | Expected open circuit voltage [V] |
String Number | 1 -217 |
Value | 1388.8 |
PV Generator | Measured open circuit voltage [V] |
String Number | 1 – 217 |
Value | 1243 – 1315 |
PV Generator | Expected short circuit current [A] |
String Number | 1 -217 |
Value | 14 |
PV Generator | Measured short circuit current [A] |
String Number | 1 – 217 |
Value | 10.5 – 13.3 |
PV Generator | Measured ambient temperature [°C] |
String Number | 1 – 217 |
Value | 28 |
PV Generator | Measured module temperature [°C] |
String Number | 1 – 217 |
Value | 35 |
PV Generator | Measured solar insulation [W/m²] |
String Number | 1 – 217 |
Value | 182 |
PV Generator | Measured insulation resistance [Mega Ohm] |
String Number | 1 – 217 |
Value | 160 |
PV Generator | General visual inspection observations |
String Number | 1 – 217 |
Value | Pass |
PV Generator | Surge Protective Devices functional (indicator at device)? |
String Number | 1 – 217 |
Value | Pass |
PV Generator | Overcurrent protection operational (correct fuse rating)? |
String Number | 1 – 217 |
Value | Pass |
PV Generator | String cables fixed and cables without damages |
String Number | 1 – 217 |
Value | Pass |
PV Generator | Connectors properly connected under no mechanical strain |
String Number | 1 – 27 |
Value | Pass |
Inverter/Charge Controller | General visual inspection observations |
String Number | 1 – 16 |
Reference | Pass |
Inverter/Charge Controller | Inverter protection settings programmed to local requirements? |
String Number | 1 – 16 |
Reference | Pass |
Inverter/Charge Controller | Means of isolating the inverter been provided on the AC side? |
String Number | 1 – 16 |
Reference | Pass |
Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
String Number | 1 -16 |
Reference | Pass |
Battery Storage | General visual inspection observations |
String Number | 1 |
Reference | Pass |
Battery Storage | Wiring properly done without visual deficits |
String Number | 1 |
Reference | Pass |
Battery Storage | Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations |
String Number | 1 |
Reference | Pass |
Battery Storage | Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …) |
String Number | 1 |
Reference | Pass |
Battery Storage | State of charge (If applicable state of health) |
String Number | 1 |
Reference | Pass |
Battery Storage | Safety measures for the respective types of batteries applied |
String Number | 1 |
Reference | Pass |
Battery Storage | Deep discharge protection, over-charge protection and temperature monitoring installed and functional |
String Number | 1 |
Reference | Pass |
Battery Storage | Cell voltage |
String Number | 1 |
Reference | Pass |
Battery Storage | Cell impedance |
String Number | 1 |
Reference | Pass |
Battery Storage | Cell temperature |
String Number | 1 |
Reference | Pass |
General Safety/Security | General visual inspection observations |
Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/NEMSA-Official-Letter-of-Request-1-1.pdf |
PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/CS-Datasheet-HiKu6_CS6W-MS_v2.4_F35A_EN_530-555W.pdf |
Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/SUN2000-200KTL-H2-Datasheet-20230822-2.pdf |
Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/NEMSA-STS-1.pdf |
Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/LUNA2000-20MWH-1H01H12H1.pdf |
Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/EEP-UNIABUJA-PV-E-013-Earthing-Layout-1.0-2.pdf |