Admin Request for Inspection REA Solar Mini Grid
Application for | REA Solar Mini-Grid Project |
---|---|
REA Code | REA-NEP-MG |
REA LOT Number | n/a |
REA-NEP-MG | PBG |
Register as | Corporate |
NEMSA Certificate Number | CC/CEIF/PR/04431 |
First Name | Donald |
Last Name | Ntekim |
Other Name | Ani |
Position | Project Manager |
Phone | 07010459245 |
donald_ntekim_ng_@huskpowersystems.com | |
Address |
Lokogoma, Abuja. |
State | Federal Capital Territory |
Company Name | Husk Power Energy Systems |
Company Email | info@huskpowersystems.com |
Company Phone | 08097814273 |
Tax Registration Number | 6500209934 |
Address |
Plot 25, Ndola Crescent, Wuse Zone 5, Abuja. |
State | Federal Capital Territory |
Name of the Village/Community | Ruttu |
State | Nasarawa |
Local Government Area | Doma |
Number of Inhabitants | 2000 |
GPS Coordinates | 8.431942 8.236074 |
Site Address/Detail Description |
Take Hospital Rd to Lafia – Shandam Rd. Then Drive from Doma-Lafia Rd to Keffin/Wambai, Take the ferry and alight at the stop. Then take a Slight left and continue into Ruttu. |
Activities | Business Activity, Administrative Facility, Educational Facility, Health Care Facility, Residential |
Total Solar PV Installed (kWp) | 50 |
Total Solar PV Energy Produce Per Day (kwh) | 2971 |
Total Storage Capacity (kwh) | 180 |
Total Load/Energy Requirement (kWh) | 1700 |
Storage Technology/Manufacturer | VRLA / Amara Raja |
Type of Coupling (AC/DC) | DC |
Generator Rated Power (kVA) | 30 |
Year of Construction | 2024 |
Fuel Type | Diesel |
Generator Model/Manufacturer | 3445 TCIGM-C2 Powerol by Mahindra |
Operation | Manual |
Date of Installation of Mini-Grid | January 15, 2024 |
Date of Application | August 13, 2024 |
Mini-Grid Owner (Full Name) | Husk Power Systems |
Phone | 08097814273 |
info@huskpowersystems.com | |
Manufacturer | First Solar |
Model | Series 6 |
Technology | High Efficiency Mono PERC with Half-cut technology. |
STC power (Wp) | 430 |
Number of Cells | 264 |
MPPT Current | 2.5 |
MPPT Voltage | 220 |
Module catalogue # | First solar series 6 |
Number Series | Parallel | 3/4 |
Total Power (Wp) | 9460 |
Fuse (A) | 5 |
Surge Protection Device | 1000 VDC 20 kA |
Converter Catalogue | N/A |
Cable cross-section | 6mm (PV to combiner box) |
Manufacturer | Statcon Energia |
Model | HDB-240-050K-3P-030M2-112CO1 |
Technology | Smart Storage Inverter |
Rated Power | 50kW |
Rated Voltage | 240VAC |
Rated Current | 72.2 A |
Manufacturer | Amara Raja |
Model | IP1X21 |
Technology | VRLA |
Cell Voltage (V) | 2 V |
Battery Voltage | 240 |
C10 Capacity | 750 |
Charge Voltage | 265 |
Module Catalogue # | High Performance VRLA |
Number Series | Parallel | 120/0 |
Total C10 capacity [kWh] | 180 |
Fuse rating [A] | 160 |
Date of cell production | January 18, 2024 |
Date of installation | April 8, 2024 |
Cable cross-section [mm²] | 95 |
PV Generator | Measured open circuit voltage [V] |
String Number | 1 |
Value | 613 |
PV Generator | Measured open circuit voltage [V] |
String Number | 2 |
Value | 613 |
PV Generator | Measured open circuit voltage [V] |
String Number | 3 |
Value | 613 |
PV Generator | Measured open circuit voltage [V] |
String Number | 4 |
Value | 613 |
PV Generator | Measured open circuit voltage [V] |
String Number | 5 |
Value | 613 |
Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
String Number | 1 |
Reference | Yes |
Battery Storage | General visual inspection observations |
String Number | 1 |
Reference | Good |
Battery Storage | General visual inspection observations |
String Number | 2 |
Reference | Good |
Battery Storage | General visual inspection observations |
String Number | 3 |
Reference | Good |
Battery Storage | General visual inspection observations |
String Number | 4 |
Reference | Good |
Battery Storage | General visual inspection observations |
String Number | 5 |
Reference | Good |
General Safety/Security | All Inverters/Charge controller operating correctly? |
String Number | 1 |
Reference | SPD, FUSES, & BREAKERS ‘OK’ |
Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Letter-NEMSA_Inspection-Ruttu-Bassan-Zarangi-Angwan-Waje.pdf |
PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/FS_Series6Datasheet.pdf |
Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/DATA-SHEET-FOR-HBD-240V-50KW-NIGERIA-3.pdf |
Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/AJB-3-INPUT-3.pdf |
Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/240V-750-AH-120Cells-1Hr-1-1.pdf |
Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/HMG-NG-EL-V2-23-01-Earthing-1-3.pdf |
User ID | Donald Ntekim |