Admin Request for Inspection REA Solar Mini Grid
| Application for | REA Solar Mini-Grid Project |
|---|---|
| REA Code | REA-NEP-MG |
| REA LOT Number | N/A |
| REA-NEP-MG | PBG |
| Register as | Corporate |
| NEMSA Certificate Number | CC/CEIF/PR/04431 |
| First Name | Donald |
| Last Name | Ntekim |
| Other Name | Ani |
| Position | Project Manager |
| Phone | 07010459245 |
| donald_ntekim_ng@huskpowersystems.com | |
| Address |
Sunny Vale, Lokogoma |
| State | Federal Capital Territory |
| Company Name | Husk Power Energy Systems |
| Company Email | info@huskpowersystems.com |
| Company Phone | 08097814273 |
| Tax Registration Number | 6500209934 |
| Address |
No 25, Ndola Crescent, Wuse Zone 5, Abuja |
| State | Federal Capital Territory |
| Name of the Village/Community | Okpatta |
| State | Nasarawa |
| Local Government Area | Doma |
| Number of Inhabitants | 1500 |
| GPS Coordinates | 8.023053, 8.268607 |
| Site Address/Detail Description |
27C9+426, Akwatta 950103, Nasarawa |
| Activities | Business Activity, Administrative Facility, Educational Facility, Health Care Facility, Residential |
| Total Solar PV Installed (kWp) | 50 |
| Total Solar PV Energy Produce Per Day (kwh) | 2971 |
| Total Storage Capacity (kwh) | 2971 |
| Total Load/Energy Requirement (kWh) | 180 |
| Storage Technology/Manufacturer | VRLA/Amara raja |
| Type of Coupling (AC/DC) | DC |
| Generator Rated Power (kVA) | 30 |
| Year of Construction | 2023 |
| Fuel Type | Diesel |
| Generator Model/Manufacturer | 3445 TCIGM-C2 Powered by Mahindra |
| Operation | manual |
| Date of Installation of Mini-Grid | August 22, 2023 |
| Date of Application | August 12, 2024 |
| Mini-Grid Owner (Full Name) | Husk Power Systems |
| Phone | 08097814273 |
| info@huskpowersystems.com | |
| Manufacturer | First Solar |
| Model | Series 6 |
| Technology | High Efficiency Low LID Mono PERC with Half cut technology |
| STC power (Wp) | 430 |
| Number of Cells | 264 |
| MPPT Current | 2.5 |
| MPPT Voltage | 220 |
| Module catalogue # | First Solar Series 6 |
| Number Series | Parallel | 3/4 |
| Total Power (Wp) | 9460 |
| Fuse (A) | 5 |
| Surge Protection Device | 1000 VDC 20kA |
| Converter Catalogue | N/A |
| Cable cross-section | 6mm (PV to combiner box) |
| Manufacturer | Statcon Energia |
| Model | HDB-240-050K-3P-030M2-112CO1 |
| Technology | Smart Storage Inverter |
| Rated Power | 50kW |
| Rated Voltage | 240VAC |
| Rated Current | 72.2 A |
| Manufacturer | Amara Raja |
| Model | IP1X21 |
| Technology | VRLA |
| Cell Voltage (V) | 2V |
| Battery Voltage | 240 |
| C10 Capacity | 50 |
| Charge Voltage | 265 |
| Module Catalogue # | High Performance VRLA |
| Number Series | Parallel | 120/0 |
| Total C10 capacity [kWh] | 180 |
| Fuse rating [A] | 160 |
| Date of cell production | January 9, 2023 |
| Date of installation | August 14, 2023 |
| Cable cross-section [mm²] | 95 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 1 |
| Value | 620 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 2 |
| Value | 620 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 3 |
| Value | 620 |
| PV Generator | Measured open circuit voltage [V] |
| String Number | 4 |
| Value | 620 |
| PV Generator | Measured load circuit voltage [V] |
| String Number | 5 |
| Value | 620 |
| Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
| String Number | 1 |
| Reference | Yes |
| Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
| String Number | 2 |
| Reference | Yes |
| Battery Storage | General visual inspection observations |
| String Number | 1 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 2 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 3 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 4 |
| Reference | Good |
| Battery Storage | General visual inspection observations |
| String Number | 5 |
| Reference | Good |
| General Safety/Security | All Inverters/Charge controller operating correctly? |
| String Number | 1 |
| Reference | SPD, FUSES & BREAKERS OKAY |
| Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Introduction-Letter-NEMSA_Inspection-Okpatta-Burum-Alagye-2.pdf |
| PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/First-solar-2.pdf |
| Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/DATA-SHEET-FOR-HBD-240V-50KW-NIGERIA-2.pdf |
| Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/AJB-3-INPUT-2.pdf |
| Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/240V-750-AH-120Cells-1Hr-1-3.pdf |
| Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/HMG-NG-EL-V2-23-01-Earthing-1-2.pdf |