Admin Request for Inspection REA Solar Mini Grid
| Application for | REA Solar Mini-Grid Project |
|---|---|
| REA Code | REA-NEP-MG |
| REA LOT Number | 6 |
| REA-NEP-MG | EEP2 |
| Register as | Individual |
| NEMSA Certificate Number | A01372 |
| First Name | jad |
| Last Name | Zeineddine |
| Position | Authorized Signatory |
| Phone | +96178940628 |
| jadzein619@gmail.com | |
| Address |
Brains & Hammers Estate, Lifecamp, Abuja, Nigeria |
| State | Federal Capital Territory |
| Name of the Village/Community | Federal University of Gashua |
| State | Yobe |
| Local Government Area | Bade |
| Number of Inhabitants | 1000 |
| GPS Coordinates | 12°52’54.14″N, 11° 0’46.17″E |
| Site Address/Detail Description |
LOT6- EEP2 – NEP- Federal University of Gashua |
| Activities | Educational Facility |
| Total Solar PV Installed (kWp) | 1800 |
| Total Solar PV Energy Produce Per Day (kwh) | 6000 |
| Total Storage Capacity (kwh) | 4129 |
| Total Load/Energy Requirement (kWh) | 4984 |
| Storage Technology/Manufacturer | Sungrow Lithium |
| Type of Coupling (AC/DC) | AC |
| Generator Rated Power (kVA) | 1320 |
| Year of Construction | 2023 |
| Fuel Type | Diesel |
| Generator Model/Manufacturer | FG Wilson P550-3 , FG Wilson P220-3 |
| Operation | Standby |
| Date of Installation of Mini-Grid | May 9, 2024 |
| Date of Application | June 10, 2024 |
| Manufacturer | Znshine Solar |
| Model | ZXM7-SHLD144-545/M |
| Technology | PERC Double Glass |
| STC power (Wp) | 545 |
| Number of Cells | 144 |
| MPPT Current | 13.11 |
| MPPT Voltage | 41.6 |
| Module catalogue # | ZXM7-SHLD144-545/M |
| Number Series | Parallel | 28/118 |
| Total Power (Wp) | 15260 |
| Fuse (A) | Built in On-Grid Inverter |
| Surge Protection Device | Built in On-Grid Inverter |
| Converter Catalogue | Built in On-Grid Inverter |
| Cable cross-section | 4mm2 |
| Manufacturer | Sungrow |
| Model | SG320HX |
| Technology | Multi-MPPT String Inverter for 1500 Vdc System |
| Rated Power | 320KW |
| Rated Voltage | 800V |
| Rated Current | 254A |
| Manufacturer | Sungrow |
| Model | SC1375UD |
| Technology | Power Conversion System |
| Rated Power | 1375KVA |
| Rated Voltage | 550V |
| Rated Current | 1443A |
| Manufacturer | CATL |
| Model | CATL 280Ah (0.5C) |
| Technology | LFP/Gr |
| Cell Voltage (V) | 3.2 |
| Battery Voltage | 51.2V |
| C10 Capacity | 14336Wh |
| Charge Voltage | 40-58.4V |
| Module Catalogue # | ST4129kWh |
| Number Series | Parallel | 384/12 |
| Total C10 capacity [kWh] | 14.34 |
| Fuse rating [A] | 400A |
| Date of cell production | July 12, 2023 |
| Date of installation | December 10, 2023 |
| Cable cross-section [mm²] | 185mm2 |
| PV Generator | Measured insulation resistance [Mega Ohm] |
| String Number | 1 |
| Value | 11.2 |
| Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
| String Number | 1 |
| Reference | yes |
| Battery Storage | Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …) |
| String Number | 1 |
| Reference | yes |
| General Safety/Security | General visual inspection observations |
| String Number | 1 |
| Reference | yes |
| Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Request-Letter-LOT6-ZNSHINE-1.pdf |
| PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/PV-Module-Datasheet-2.pdf |
| Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/On-Grid-Inverter-Datasheet-1.pdf |
| Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/PCS-Datasheet-1.pdf |
| Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/BESS-Solution-1.pdf |
| Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Lightning-Protection-SLD-1.pdf |
| User ID | Jad Zeineddine |