Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number 250
REA-NEP-MG PBG
Inspectorate Field Office closest to site location Abuja
Register as Corporate
NEMSA Certificate Number CC/CEIF/PR/03425
First Name Anthony
Last Name Uchechukwu
Other Name Luca
Position Operations Officer
Phone 09062798374
Email lucatony73@gmail.com
Address

Plot 414 A Close, Gwarinpa Estate, Abuja.

State Federal Capital Territory
Company Name NEBULAR ENGINEERING SOLUTIONS LTD.
Company Email nebular.engr@gmail.com
Company Phone 08104830579
Tax Registration Number 21120361-0001
Address

Plot 414 A Close, Gwarinpa Estate, Abuja.

State Federal Capital Territory
Name of the Village/Community Barkin Ayini
State Nasarawa
Local Government Area Kokona
Number of Inhabitants 3500
GPS Coordinates 8.668329, 8.058965
Site Address/Detail Description

The site is located in this coordinate 8.76713, 7.585397, in Barkin Ayini community, Kokona LGA of Nasarawa State under the REA NEP Performance Based Grant. The project is aimed at providing reliable electricity to 255 Households, 10 Commercial Users, 2 special centres, including Health Centre and 3 industrial.

Activities Business Activity, Administrative Facility, Educational Facility, Health Care Facility, Residential, Religion
Total Solar PV Installed (kWp) 79.2
Total Solar PV Energy Produce Per Day (kwh) 950
Total Storage Capacity (kwh) 150
Total Load/Energy Requirement (kWh) 20
Storage Technology/Manufacturer Li-on/Life PO4
Type of Coupling (AC/DC) DC Coupled
Generator Rated Power (kVA) 200
Year of Construction 2022
Fuel Type Diesel
Generator Model/Manufacturer FG WILSON
Operation Auto/Backup
Date of Installation of Mini-Grid December 1, 2024
Date of Application January 31, 2024
Mini-Grid Owner (Full Name) NEBULAR ENGINEERING SOLUTIONS LTD.
Phone 08104830579
Email nebular.engr@gmail.com

Manufacturer Sora
Model 550M
Technology Monocrystralline
STC power (Wp) 550
Number of Cells 144
MPPT Current 13.01A
MPPT Voltage 42.31

Module catalogue # 144
Number Series | Parallel 12| 12
Total Power (Wp) 79.2kWp
Fuse (A) 32
Surge Protection Device SPD 1000Vdc
Converter Catalogue Galaxy Solar
Cable cross-section 4mmsqr

Manufacturer Galaxy Solar
Model MGSP5K
Technology Hybrid Inverter
Rated Power 5kW
Rated Voltage 110V
Rated Current 110V

Manufacturer LiFePO4
Model VG48300
Technology Li-on
Cell Voltage (V) 51.2V
Battery Voltage 51.2V
C10 Capacity 5kWh
Charge Voltage 57.6V

Module Catalogue # 10
Number Series | Parallel 10 Parallel
Total C10 capacity [kWh] 150kWh
Fuse rating [A] 200
Date of cell production July 7, 2023
Date of installation January 15, 2023
Cable cross-section [mm²] 35mmsqr

PV Generator Expected open circuit voltage [V]
String Number 2
Value 49.9VDC
PV Generator Measured open circuit voltage [V]
String Number 2
Value Yes
PV Generator Overcurrent protection operational (correct fuse rating)?
String Number 2
Value 20A
PV Generator String cables fixed and cables without damages
String Number 2
Value Yes
PV Generator Result of verification of measured values (OK, low, …)
String Number 2
Value ok
PV Generator Measured module temperature [°C]
String Number 2
Value 45.8VDC

Inverter/Charge Controller General visual inspection observations
String Number 3
Reference ok
Inverter/Charge Controller Inverter protection settings programmed to local requirements?
String Number 3
Reference yes
Inverter/Charge Controller When an RCD is installed to the AC circuit feeding an inverter, the RCD type shall be verified to ensure it has been selected according to the requirements of IEC 60364
String Number 3
Reference yes
Inverter/Charge Controller All Inverters/Charge controller operating correctly?
String Number 3
Reference yes

Battery Storage General visual inspection observations
String Number 4
Reference Ok
Battery Storage Wiring properly done without visual deficits
String Number 4
Reference Yes
Battery Storage Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations
String Number 4
Reference OK
Battery Storage Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …)
String Number 4
Reference OK
Battery Storage State of charge (If applicable state of health)
String Number 4
Reference ok

General Safety/Security General visual inspection observations
String Number 5
Reference ok
General Safety/Security Inverter protection settings programmed to local requirements?
String Number 5
Reference ok
General Safety/Security When an RCD is installed to the AC circuit feeding an inverter, the RCD type shall be verified to ensure it has been selected according to the requirements of IEC 60364
String Number 5
Reference yes
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Nebluar-Mini-Grid-_-Request-for-Inspection-and-Certification-of-Barkin-Ayini-Iwa-sabo-Jijipe-and-3.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/BARKIN-AYINI-PV-System-1.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/SLD-for-Charge-controller-3-150×150.png
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/Combiner-Boxes-3.pdf
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/BARKIN-AYINI-Battery-System.pdf
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Earthing-and-Surge-protection-system-2.pdf
User ID Luca Tony