Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number 266
REA-NEP-MG PBG
Inspectorate Field Office closest to site location Jos
Register as Corporate
NEMSA Certificate Number CC/CEIF/PR/03425
First Name ANTHONY
Last Name UCHECHUKWU
Other Name LUCA
Position OPERATIONS OFFICER
Phone 09062798374
Email lucatony73@gmail.com
Address

House No 44 Agape Street, Jikwoyi Phase 2, Abuja.

State Federal Capital Territory
Company Name NEBULAR ENGINEERING SOLUTIONS LTD.
Company Email nebular.engr@gmail.com
Company Phone 08104830579
Tax Registration Number 21120361-0001
Address

PLOT 414, A CLOSE, GWARIMPA ESTATE, ABUJA.

State Federal Capital Territory
Name of the Village/Community Namu
State Plateau
Local Government Area Qua’an Pan
Number of Inhabitants 15000
GPS Coordinates 8.689481,9.097548
Site Address/Detail Description

The site is located in this coordinate 8.689481,9.097548, in Namu community, Quan’an Pan LGA of Plateau State under the REA NEP Performance Based Grant. The project is aimed at providing reliable electricity to 1920 Households, 232 Commercial Users, 30 Health center, 35 Religious center and 37 Public User in the community.

Activities Business Activity, Administrative Facility, Educational Facility, Health Care Facility, Residential, Religious
Total Solar PV Installed (kWp) 199.5
Total Solar PV Energy Produce Per Day (kwh) 1500
Total Storage Capacity (kwh) 300kWh
Total Load/Energy Requirement (kWh) 30
Storage Technology/Manufacturer BYD
Type of Coupling (AC/DC) DC
Generator Rated Power (kVA) 200
Year of Construction 2022
Fuel Type Diesel
Generator Model/Manufacturer FG WILSON
Operation Auto/Backup
Date of Installation of Mini-Grid December 1, 2023
Date of Application December 8, 2023
Mini-Grid Owner (Full Name) NEBULAR ENGINEERING SOLUTIONS LTD.
Phone 08104830579
Email nebular.engr@gmail.com

Manufacturer JA Solar
Model JAm72S30-555/GR
Technology MONOCRYSTALLINE
STC power (Wp) 555
Number of Cells 144
MPPT Current 13.18A
MPPT Voltage 42.11VDC

Module catalogue # 366
Number Series | Parallel 15/20
Total Power (Wp) 199.4KWP
Fuse (A) 32A
Surge Protection Device SPD 1000Vdc
Converter Catalogue Deye
Cable cross-section 4mmsqr

Manufacturer DEYE
Model SUN-12K-SG04LP3-EU
Technology Hybrid
Rated Power 12KW
Rated Voltage 12kW
Rated Current 240ADC

Manufacturer BYD
Model LV Flex Lite
Technology LITHIUM ION
Cell Voltage (V) 51.2V
Battery Voltage 51.2V
C10 Capacity 5kWh
Charge Voltage 57.6V

Module Catalogue # 10
Number Series | Parallel 6 Parallel | 10 Banks
Total C10 capacity [kWh] 300kWh
Fuse rating [A] 200
Date of cell production July 7, 2022
Date of installation November 30, 2023
Cable cross-section [mm²] 70mmsqr

PV Generator Overcurrent protection operational (correct fuse rating)?
String Number 13
Value 20A
PV Generator Connectors properly connected under no mechanical strain
String Number 13
Value YES
PV Generator Surge Protective Devices functional (indicator at device)?
String Number 13
Value YES
PV Generator Expected open circuit voltage [V]
String Number 13
Value 49.9VDC
PV Generator General visual inspection observations
String Number 13
Value OK
PV Generator Measured open circuit voltage [V]
String Number 13
Value 45.8VDC
PV Generator Measured module temperature [°C]
String Number 13
Value 36
PV Generator Measured earth resistance of support structure [Ohm]
String Number 13
Value 1.2OHMS
PV Generator Measured insulation resistance [Mega Ohm]
String Number 13
Value 3360OHMS

Inverter/Charge Controller General visual inspection observations
String Number 3
Reference OK
Inverter/Charge Controller Inverter protection settings programmed to local requirements?
String Number 3
Reference OK
Inverter/Charge Controller Means of isolating the inverter been provided on the AC side?
String Number 3
Reference OK
Inverter/Charge Controller Inverter/charge controller protection settings and installer details displayed on site?
String Number 3
Reference OK

Battery Storage General visual inspection observations
String Number 16
Reference ok
Battery Storage Cell temperature
String Number 16
Reference 20-60

General Safety/Security General visual inspection observations
String Number 1
Reference ok
General Safety/Security Inverter/charge controller protection settings and installer details displayed on site?
String Number 3
Reference ok
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Nebluar-Mini-Grid-_-Request-for-Inspection-and-Certification-of-Namu-Ajaga-and-Ajigwara.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/SLD-for-Charge-controller-150×150.png
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/Namu-PV-System.pdf
Battery System
User ID Anthony Luca Uchechukwu