Admin Request for Inspection REA Solar Mini Grid
Application for | REA Solar Mini-Grid Project |
---|---|
REA Code | REA-NEP-MG |
REA LOT Number | 0118 |
REA-NEP-MG | PBG |
Blank | Ilorin |
Register as | Corporate |
NEMSA Certificate Number | CC/CEIF/PR/00285 |
First Name | DOTUN |
Last Name | TOKUN |
Position | MANAGING DIRECTOR |
Phone | 08034016045 |
DOTUNTOKUN@SOLARMATENG.COM | |
Address |
21 OGUNTONA CRESCENT, GBAGADA PHASE 1 |
State | Lagos |
Company Name | SOLARMATE ENGINEERING LIMITED |
Company Email | DOTUNTOKUN@SOLARMATENG.COM |
Company Phone | 07038000733 |
Tax Registration Number | 01159079-0001 |
Address |
21 OGUNTONA CRESCENT, GBAGADA PHASE 1 |
State | Lagos |
Name of the Village/Community | BAGAJI ODO |
State | Kogi |
Local Government Area | Omala |
Number of Inhabitants | 623 |
GPS Coordinates | LAT: 7.945771°, LONG: 7.591889° |
Site Address/Detail Description |
BAGAJI ODO COMMUNITY |
Activities | Business Activity, Educational Facility, Health Care Facility, Residential |
Total Solar PV Installed (kWp) | 56.68 |
Total Solar PV Energy Produce Per Day (kwh) | 255.06 |
Total Storage Capacity (kwh) | 80KWh |
Total Load/Energy Requirement (kWh) | 18.69 |
Storage Technology/Manufacturer | LITHIUM-ION/PYLONTECH |
Type of Coupling (AC/DC) | AC/DC |
Generator Rated Power (kVA) | 150KVA |
Year of Construction | 2023 |
Fuel Type | Diesel |
Generator Model/Manufacturer | JMG |
Operation | MANUAL/AUTOMATIC |
Date of Installation of Mini-Grid | December 5, 2023 |
Date of Application | December 4, 2023 |
Mini-Grid Owner (Full Name) | PRIVIDA POWER LIMITED |
Phone | 08037404111 |
A.USIFO@PRIVIDAENERGY.COM | |
Applicant | SOLARMATE ENGINEEING LIMITED |
Phone | 08034016045 |
DOTUNTOKUN@SOLARMATENG.COM | |
Manufacturer | ULICA |
Model | UL-545M-144HV |
Technology | MONO-HALF CUT |
STC power (Wp) | 545 |
Number of Cells | 144 |
MPPT Current | 13.04A |
MPPT Voltage | 41.8VDC |
Module catalogue # | 1 |
Number Series | Parallel | 13/8 |
Total Power (Wp) | 56680Wp |
Fuse (A) | 20 |
Surge Protection Device | 40KA |
Converter Catalogue | ULICA |
Cable cross-section | 4MMSQ |
Manufacturer | DEYE |
Model | SUN-12K-SG04LP3-EU |
Technology | HYRID |
Rated Power | 48KW |
Rated Voltage | 48VDC |
Rated Current | 240A |
Manufacturer | PYLONTECH |
Model | UP5000 |
Technology | LITHIUM-ION |
Cell Voltage (V) | 2.13V |
Battery Voltage | 48VDC |
C10 Capacity | 0.2C |
Charge Voltage | 75A |
Module Catalogue # | 1 |
Number Series | Parallel | 1/16 |
Total C10 capacity [kWh] | 80KWh |
Fuse rating [A] | 300 |
Date of cell production | September 20, 2022 |
Date of installation | December 5, 2023 |
Cable cross-section [mm²] | 70MMSQ |
PV Generator | Overcurrent protection operational (correct fuse rating)? |
String Number | 13 |
Value | 20A |
PV Generator | Surge Protective Devices functional (indicator at device)? |
String Number | 13 |
Value | YES |
PV Generator | Connectors properly connected under no mechanical strain |
String Number | 13 |
Value | YES |
PV Generator | General visual inspection observations |
String Number | 13 |
Value | OK |
PV Generator | Expected open circuit voltage [V] |
String Number | 13 |
Value | 49.9VDC |
PV Generator | Measured open circuit voltage [V] |
String Number | 13 |
Value | 48VDC |
PV Generator | Measured module temperature [°C] |
String Number | 13 |
Value | 38 |
PV Generator | Measured earth resistance of support structure [Ohm] |
String Number | 13 |
Value | 1.6OHMS |
PV Generator | Measured insulation resistance [Mega Ohm] |
String Number | 13 |
Value | 2870MOHMS |
Inverter/Charge Controller | General visual inspection observations |
String Number | 4 |
Reference | OK |
Inverter/Charge Controller | Inverter protection settings programmed to local requirements? |
String Number | 4 |
Reference | OK |
Inverter/Charge Controller | Means of isolating the inverter been provided on the AC side? |
String Number | 4 |
Reference | OK |
Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
String Number | 4 |
Reference | OK |
Inverter/Charge Controller | Inverter/charge controller protection settings and installer details displayed on site? |
String Number | 4 |
Reference | OK |
Battery Storage | General visual inspection observations |
String Number | 16 |
Reference | OK |
Battery Storage | Wiring properly done without visual deficits |
String Number | 16 |
Reference | OK |
Battery Storage | Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations |
String Number | 16 |
Reference | OK |
Battery Storage | Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …) |
String Number | 16 |
Reference | OK |
Battery Storage | State of charge (If applicable state of health) |
String Number | 16 |
Reference | OK |
Battery Storage | Number of full cycles calculated by the monitoring system (if applicable) |
String Number | 24 |
Reference | OK |
Battery Storage | Cell voltage |
String Number | 16 |
Reference | 2.1VDC |
Battery Storage | Cell temperature |
String Number | 16 |
Reference | 20-60 |
General Safety/Security | General visual inspection observations |
String Number | 1 |
Reference | OK |
General Safety/Security | Inverter protection settings programmed to local requirements? |
String Number | 4 |
Reference | OK |
General Safety/Security | Means of isolating the inverter been provided on the AC side? |
String Number | 4 |
Reference | OK |
General Safety/Security | All Inverters/Charge controller operating correctly? |
String Number | 4 |
Reference | OK |
General Safety/Security | Inverter/charge controller protection settings and installer details displayed on site? |
String Number | 4 |
Reference | OK |
Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Request-for-inspections-to-NEMSA-6-MINIGRIDS-KOGI-STATE-1.pdf |
PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/BAGAJI-ODO-SLD.pdf |
Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/INVERTER-SLD-5.pdf |
Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/BAGAJI-ODO-PV-PROTECTION-BOX-SLD.pdf |
Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/BAGAJI-ODO-BATTERY-SLD.pdf |
Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/BAGAJI-ODO-EARTHING.pdf |
User ID | DOTUN TOKUN |