Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number 289
REA-NEP-MG PBG
Inspectorate Field Office closest to site location Akure
Register as Corporate
NEMSA Certificate Number CC/CEIF/PR/00609
First Name Joseph
Last Name Ojo
Position Chief Business Officer
Phone 07039476932
Email j.ojo@a4tintegrated.com
Address

27b, Olumoroti Jaiyesimi street, Gbagada Phase 2, Lagos

State Lagos
Company Name A4&T Power Solutions
Company Email info@a4tintegrated.com
Company Phone 07039476932
Tax Registration Number 20022603-0001
Address

27b, Olumoroti Jaiyesimi street, Gbagada phase 2, Lagos

State Lagos
Name of the Village/Community Epe
State Ondo
Local Government Area Ondo East
Number of Inhabitants 2500
GPS Coordinates Lat: 7.173017, Long: 4.776711
Site Address/Detail Description

Epe is a community in Ondo East Local Government of Ondo State. The community is characterized by households, cocoa farming, and other agro-processing activities. The community has a population of over 2000

Activities Business Activity, Educational Facility, Health Care Facility, Residential
Total Solar PV Installed (kWp) 51.2
Total Solar PV Energy Produce Per Day (kwh) 133.12
Total Storage Capacity (kwh) 90
Total Load/Energy Requirement (kWh) 115.31
Storage Technology/Manufacturer lithium/Felicity
Type of Coupling (AC/DC) DC
Generator Rated Power (kVA) 60
Year of Construction 2022
Fuel Type Diesel
Generator Model/Manufacturer Perkins
Operation Automatic
Date of Installation of Mini-Grid August 1, 2023
Date of Application August 10, 2023
Mini-Grid Owner (Full Name) A4&T Power Solutions Limited
Phone 08054016128
Email info@a4tintegrated.com

Manufacturer Jinko
Model JKM400M-6RL3-V
Technology Monocrstalline
STC power (Wp) 400
Number of Cells 72
MPPT Current 80Amps
MPPT Voltage 150V

Module catalogue # 10
Number Series | Parallel 10-12
Total Power (Wp) 4000
Fuse (A) 10
Surge Protection Device Yes
Converter Catalogue Yes
Cable cross-section 10mm

Manufacturer Just Stand Out
Model JSO12048165
Technology PV INVERTER
Rated Power 12KW
Rated Voltage 48V
Rated Current 50

Manufacturer Felicity
Model LPBF Series 48250-48300
Technology Lithium
Cell Voltage (V) 48V
Battery Voltage 48V
C10 Capacity 30A
Charge Voltage 57.6

Module Catalogue # LPBF Series 48250-48300
Number Series | Parallel 1
Total C10 capacity [kWh] 7.2
Fuse rating [A] 120
Date of cell production December 5, 2022
Cable cross-section [mm²] 120

PV Generator Expected open circuit voltage [V]
String Number 1
Value 441.2
PV Generator Measured open circuit voltage [V]
String Number 1
Value 352.96
PV Generator Expected load circuit voltage [V]
String Number 1
Value 366.7
PV Generator Measured load circuit voltage [V]
String Number 1
Value 293.4
PV Generator Expected short circuit current [A]
String Number 1
Value 11.57
PV Generator Measured short circuit current [A]
String Number 1
Value 9.256
PV Generator Measured ambient temperature [°C]
String Number 1
Value 20
PV Generator Measured module temperature [°C]
String Number 1
Value 45
PV Generator Expected power output [kW]
String Number 1
Value 4000
PV Generator Measured power output [kW]
String Number 1
Value 3200
PV Generator General visual inspection observations
String Number 1
Value OK
PV Generator Surge Protective Devices functional (indicator at device)?
String Number 1
Value YES
PV Generator Overcurrent protection operational (correct fuse rating)?
String Number 1
Value 20
PV Generator String cables fixed and cables without damages
String Number 1
Value OK

Inverter/Charge Controller General visual inspection observations
String Number 1
Reference OK
Inverter/Charge Controller Inverter protection settings programmed to local requirements?
String Number 1
Reference OK
Inverter/Charge Controller When an RCD is installed to the AC circuit feeding an inverter, the RCD type shall be verified to ensure it has been selected according to the requirements of IEC 60364
String Number 1
Reference YES
Inverter/Charge Controller Means of isolating the inverter been provided on the AC side?
String Number 1
Reference YES
Inverter/Charge Controller All Inverters/Charge controller operating correctly?
String Number 1
Reference OK
Inverter/Charge Controller Inverter/charge controller protection settings and installer details displayed on site?
String Number 1
Reference OK

Battery Storage General visual inspection observations
String Number 1
Reference OK
Battery Storage Wiring properly done without visual deficits
String Number 1
Reference YES
Battery Storage Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations
String Number 1
Reference YES
Battery Storage Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …)
String Number 1
Reference YES
Battery Storage State of charge (If applicable state of health)
String Number 1
Reference OK
Battery Storage Safety measures for the respective types of batteries applied
String Number 1
Reference YES
Battery Storage Deep discharge protection, over-charge protection and temperature monitoring installed and functional
String Number 1
Reference YES
Battery Storage Number of full cycles calculated by the monitoring system (if applicable)
String Number 1
Reference YES
Battery Storage Cell voltage
String Number 1
Reference 48V
Battery Storage Cell temperature
String Number 1
Reference 20

General Safety/Security General visual inspection observations
String Number 1
Reference OK
General Safety/Security Inverter protection settings programmed to local requirements?
String Number 1
Reference YES
General Safety/Security When an RCD is installed to the AC circuit feeding an inverter, the RCD type shall be verified to ensure it has been selected according to the requirements of IEC 60364
String Number 1
Reference YES
General Safety/Security Means of isolating the inverter been provided on the AC side?
String Number 1
Reference YES
General Safety/Security Isolating and switching devices been connected such that PC installation is wired to the “load” side and the public supply to the “source” side?
String Number 1
Reference YES
General Safety/Security All Inverters/Charge controller operating correctly?
String Number 1
Reference YES
General Safety/Security Inverter/charge controller protection settings and installer details displayed on site?
String Number 1
Reference YES
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Letter-for-Inspection-Request-Epe-Ondo-State.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/PV-SYSTEM-EPE.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/JSO-SMART-INVERTERS.pdf
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/COMBINER-BOX-3.pdf
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/BATTERY-SYSTEM-CONFIGURATION-EPE.pdf
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Earthing-System-Surge-Protection.docx-3.pdf
User ID Joseph Ojo