Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number 054
REA-NEP-MG PBG
Inspectorate Field Office closest to site location Akure
Register as Corporate
NEMSA Certificate Number CC/CEIF/PR00609
First Name Joseph
Last Name Ojo
Position Chief Business Officer
Phone 07039476932
Email j.ojo@a4tintegrated.com
Address

No 27B, Olumoroti Jayeisimi Street, Gbagada Phase 2, Lagos

State Lagos
Company Name A4&T Power Solutions
Company Email info@a4tintegrated.com
Company Phone 07039476932
Tax Registration Number 20022603-0001
Address

No 27B, Olumoroti Jayeisimi Street, Gbagada Phase 2, Lagos

State Lagos
Name of the Village/Community Ilugha
State Ondo
Local Government Area Ondo West
Number of Inhabitants 4000
GPS Coordinates Lat: 6.91493, Long: 4.646107
Site Address/Detail Description

Ilugha Community, Ondo West LGA, Ondo State.

Activities Business Activity, Health Care Facility, Residential, Public Institutions
Total Solar PV Installed (kWp) 52.8
Total Solar PV Energy Produce Per Day (kwh) 154.44
Total Storage Capacity (kwh) 90
Total Load/Energy Requirement (kWh) 248.52
Storage Technology/Manufacturer Lithium/Felicity
Type of Coupling (AC/DC) DC
Generator Rated Power (kVA) 60
Year of Construction 2023
Fuel Type Diesel
Generator Model/Manufacturer Perkins
Operation Automatic
Date of Installation of Mini-Grid April 10, 2023
Date of Application June 5, 2023

Manufacturer Jinko
Model JKM400M-6RL3-V
Technology Monocrstalline
STC power (Wp) 400
Number of Cells 72
MPPT Current 80Amps
MPPT Voltage 150V

Module catalogue # 10
Number Series | Parallel 9-3
Total Power (Wp) 32
Fuse (A) 250
Surge Protection Device 20KA/40KA
Converter Catalogue 0
Cable cross-section 10mm2

Manufacturer Just Stand Out
Model JSO12048165
Technology MPPT
Rated Power 15600
Rated Voltage 800
Rated Current 80

Manufacturer Felicity
Model LPBF Series 48300
Technology Lithium
Cell Voltage (V) 48
Battery Voltage 48V
C10 Capacity 0
Charge Voltage 51.2

Module Catalogue # LPBF Series 48300
Number Series | Parallel 1-6 in parallel
Total C10 capacity [kWh] 90
Fuse rating [A] 250
Date of cell production January 15, 2022
Date of installation May 15, 2023
Cable cross-section [mm²] 120

PV Generator Expected open circuit voltage [V]
String Number 1
Value 448.2
PV Generator Measured open circuit voltage [V]
String Number 1
Value 291.33
PV Generator Expected load circuit voltage [V]
String Number 1
Value 375.3
PV Generator Measured load circuit voltage [V]
String Number 1
Value 243.95
PV Generator Expected short circuit current [A]
String Number 1
Value 10.36A
PV Generator Expected power output [kW]
String Number 1
Value 3600W
PV Generator Measured power output [kW]
String Number 1
Value 2340W
PV Generator Measured earth resistance of support structure [Ohm]
String Number 1
Value 0.5
PV Generator General visual inspection observations
String Number 1
Value Ok
PV Generator Surge Protective Devices functional (indicator at device)?
String Number 1
Value Available
PV Generator String cables fixed and cables without damages
String Number 1
Value ok
PV Generator Overcurrent protection operational (correct fuse rating)?
String Number 1
Value Available
PV Generator Connectors properly connected under no mechanical strain
String Number 1
Value Ok

Inverter/Charge Controller General visual inspection observations
String Number 1
Reference OK
Inverter/Charge Controller Inverter protection settings programmed to local requirements?
String Number 1
Reference ok
Inverter/Charge Controller Isolating and switching devices been connected such that PC installation is wired to the “load” side and the public supply to the “source” side?
String Number 1
Reference Available
Inverter/Charge Controller All Inverters/Charge controller operating correctly?
String Number 1
Reference 0k
Inverter/Charge Controller Inverter/charge controller protection settings and installer details displayed on site?
String Number 1
Reference Ok
Inverter/Charge Controller Means of isolating the inverter been provided on the AC side?
String Number 1
Reference Available

Battery Storage General visual inspection observations
String Number 1
Reference OK
Battery Storage Wiring properly done without visual deficits
String Number 1
Reference Done
Battery Storage Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations
String Number 1
Reference Done
Battery Storage Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …)
String Number 1
Reference Done
Battery Storage Safety measures for the respective types of batteries applied
String Number 1
Reference Done
Battery Storage Deep discharge protection, over-charge protection and temperature monitoring installed and functional
String Number 1
Reference Available
Battery Storage Cell voltage
String Number 1
Reference 48
Battery Storage Cell temperature
String Number 1
Reference 25
Battery Storage Number of full cycles calculated by the monitoring system (if applicable)
String Number 1
Reference 6000

General Safety/Security General visual inspection observations
String Number 1
Reference OK
General Safety/Security Inverter protection settings programmed to local requirements?
String Number 1
Reference Done
General Safety/Security Means of isolating the inverter been provided on the AC side?
String Number 1
Reference Available
General Safety/Security Isolating and switching devices been connected such that PC installation is wired to the “load” side and the public supply to the “source” side?
String Number 1
Reference Available
General Safety/Security All Inverters/Charge controller operating correctly?
String Number 1
Reference Ok
General Safety/Security Inverter/charge controller protection settings and installer details displayed on site?
String Number 1
Reference Ok
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Letter-of-Inspection-Application-NEMSA.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/PV-System-SLD-Technical-Specification.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/PV-System-SLD-Technical-Specification-2.pdf
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/COMBINER-BOX-4.pdf
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/BATTERY-SYSTEM-CONFIGURATION.docx-3.pdf
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Earthing-System-Surge-Protection-1.pdf
User ID Joseph Ojo