Admin Request for Inspection REA Solar Mini Grid
Application for | REA Solar Mini-Grid Project |
---|---|
REA Code | REA-NEP-MG |
REA LOT Number | n/a |
REA-NEP-MG | PBG |
Blank | Abuja |
Register as | Corporate |
NEMSA Certificate Number | CC/CEIF/PR/04431 |
First Name | Donald |
Last Name | Ntekim |
Other Name | Ani |
Position | Project Manager |
Phone | 07010459245 |
donald_ntekim_ng_@huskpowersystems.com | |
Address |
Lokogoma, Abuja. |
State | Federal Capital Territory |
Company Name | Husk power energy systems |
Company Email | info@huskpowersystems.com |
Company Phone | 08097814273 |
Tax Registration Number | 6500209934 |
Address |
836, Idris Ibrahim Crescent, Jabi District |
State | Federal Capital Territory |
Name of the Village/Community | Kiguna |
State | Nasarawa |
Local Government Area | Lafia |
Number of Inhabitants | 1100 |
GPS Coordinates | 8.654253 8.904956 |
Site Address/Detail Description |
Farin Rua, 950102, Nasarawa off Lafia Shandam road |
Activities | Business Activity, Health Care Facility, Residential |
Total Solar PV Installed (kWp) | 50 |
Total Solar PV Energy Produce Per Day (kwh) | 3100 |
Total Storage Capacity (kwh) | 180 |
Total Load/Energy Requirement (kWh) | 1500 |
Storage Technology/Manufacturer | VRLA/Amara Raja |
Type of Coupling (AC/DC) | DC |
Generator Rated Power (kVA) | 30 |
Year of Construction | 2022 |
Fuel Type | Diesel |
Generator Model/Manufacturer | 3445 TCIGM-C2 Powerol by Mahindra |
Operation | Manual |
Date of Installation of Mini-Grid | July 6, 2022 |
Date of Application | January 23, 2023 |
Mini-Grid Owner (Full Name) | Husk power systems |
Phone | 08097814273 |
info@huskpowersystems.com | |
Manufacturer | Longi Solar |
Model | LR4-72HPH |
Technology | High efficiency low LID mono perc with half cut technology |
STC power (Wp) | 450 |
Number of Cells | 144 |
MPPT Current | 11.33 |
MPPT Voltage | 49.6 |
Module catalogue # | LR4-72HPH |
Number Series | Parallel | 14/2 |
Total Power (Wp) | 12.32 |
Fuse (A) | 20 |
Surge Protection Device | 1000vdc, 20kA. |
Converter Catalogue | N/A |
Cable cross-section | 4mm (PV to combiner box) |
Manufacturer | Statcon Energiaa |
Model | HBD-240-050k-3P-030M2-11-C01 |
Technology | Smart storage solar inverters |
Rated Power | 50kW |
Rated Voltage | 240VAC |
Rated Current | 72.2A |
Manufacturer | Amara Raja |
Model | IPI021 |
Technology | VRLA |
Cell Voltage (V) | 2 |
Battery Voltage | 240 |
C10 Capacity | 24 |
Charge Voltage | 276 |
Module Catalogue # | IPI021 |
Number Series | Parallel | 120 |
Total C10 capacity [kWh] | 180 |
Fuse rating [A] | 160 |
Date of cell production | February 9, 2022 |
Cable cross-section [mm²] | 95 |
General comments | Battery in Good condition |
PV Generator | Measured open circuit voltage [V] |
String Number | 8 |
Value | 616 |
PV Generator | Measured open circuit voltage [V] |
String Number | 7 |
Value | 616 |
PV Generator | Measured open circuit voltage [V] |
String Number | 6 |
Value | 616 |
PV Generator | Measured open circuit voltage [V] |
String Number | 5 |
Value | 616 |
PV Generator | Measured open circuit voltage [V] |
String Number | 4 |
Value | 616 |
PV Generator | Measured open circuit voltage [V] |
String Number | 3 |
Value | 616 |
PV Generator | Measured open circuit voltage [V] |
String Number | 2 |
Value | 616 |
PV Generator | Measured open circuit voltage [V] |
String Number | 1 |
Value | 616 |
Inverter/Charge Controller | General visual inspection observations |
String Number | 1 |
Reference | Good |
Battery Storage | Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations |
String Number | 120 |
Reference | n/a |
Battery Storage | General visual inspection observations |
String Number | 120 |
Reference | n/a |
Battery Storage | Cell voltage |
String Number | 120 |
Reference | n/a |
Battery Storage | Wiring properly done without visual deficits |
String Number | 120 |
Reference | n/a |
Battery Storage | State of charge (If applicable state of health) |
String Number | 120 |
Reference | n/a |
General Safety/Security | General visual inspection observations |
String Number | 1 |
Reference | Good |
General Safety/Security | Inverter protection settings programmed to local requirements? |
String Number | 1 |
Reference | Good |
General Safety/Security | Means of isolating the inverter been provided on the AC side? |
String Number | 1 |
Reference | Good |
General Safety/Security | All Inverters/Charge controller operating correctly? |
String Number | 1 |
Reference | Good |
Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Introduction-Letter-NEMSA_Inspection-kiguna.pdf |
PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/50kWp-SLD-1.pdf |
Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/solar-off-grid-inverter-statcon-and-utl.pdf |
Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/datasheet-longi-solar-mono-crystalline-144-cell-India-1.pdf |
Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Powerstack-Brochure-OCT-2022.pdf |
Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/lap-bx-125-ese-lightning-arrester.pdf |
User ID | Donald Ntekim |