Admin Request for Inspection REA Solar Mini Grid
Application for | REA Solar Mini-Grid Project |
---|---|
REA Code | REA-CAP-MG |
REA LOT Number | STC050 |
Blank | Abuja |
Register as | Corporate |
NEMSA Certificate Number | 32333 |
First Name | Folu |
Last Name | Alabi |
Position | Vice President, Operations |
Phone | 08060928305 |
falabi@ashipaelectric.com | |
Address |
9 Jalingo Street, Garki Area 2, Abuja. |
State | Federal Capital Territory |
Company Name | ASHIPA ELECTRIC LIMITED |
Company Email | info@ashipaelectric.com |
Company Phone | 08052305067 |
Tax Registration Number | 19193765-0001 |
Address |
9 Jalingo Street, Garki Area 2, Abuja. |
State | Federal Capital Territory |
Name of the Village/Community | Kaida-Tsoho Community |
State | Federal Capital Territory |
Local Government Area | Gwagwalada |
Number of Inhabitants | 1200 |
GPS Coordinates | 9°2’23″N, 6°56’36″E |
Site Address/Detail Description |
Kaida Tsoho is an off-grid community located around Gwagwalada area Abuja. The community is majorly an agrarian community consisting of 3 main tribes. |
Activities | Business Activity, Educational Facility, Health Care Facility, Residential |
Total Solar PV Installed (kWp) | 100 |
Total Solar PV Energy Produce Per Day (kwh) | 350 |
Total Storage Capacity (kwh) | 200 |
Total Load/Energy Requirement (kWh) | 220 |
Storage Technology/Manufacturer | Lithium Ion / Felicity Solar |
Type of Coupling (AC/DC) | DC |
Generator Rated Power (kVA) | 100 |
Year of Construction | 2022 |
Fuel Type | Diesel |
Generator Model/Manufacturer | Perkins |
Operation | Automatic |
Date of Installation of Mini-Grid | December 12, 2022 |
Date of Application | December 29, 2022 |
Mini-Grid Owner (Full Name) | Ashipa Electric Limited |
Phone | 08052305067 |
info@ashipaelectric.com | |
Manufacturer | Jinko Solar |
Model | JKM – 550W |
Technology | Monocrystalline |
STC power (Wp) | 550 |
Number of Cells | 144 |
MPPT Current | 13.07 |
MPPT Voltage | 40.56 |
Manufacturer | Jinko Solar |
Model | JKM – 560W |
Technology | Monocrystalline |
STC power (Wp) | 560 |
Number of Cells | 156 |
MPPT Current | 12.64 |
MPPT Voltage | 44.31 |
Module catalogue # | 560W |
Number Series | Parallel | 3 Series | 3 Parallel |
Total Power (Wp) | 5040 |
Fuse (A) | 63 |
Surge Protection Device | Type 2 |
Converter Catalogue | 195v, 120A |
Cable cross-section | 16sq.mm |
Module catalogue # | 550W |
Number Series | Parallel | 3 Series | 3 Parallel |
Total Power (Wp) | 4950 |
Fuse (A) | 63 |
Surge Protection Device | Type 2 |
Converter Catalogue | 195v, 120 |
Cable cross-section | 16sq.mm |
Manufacturer | Felicity Solar |
Model | SSCM12048 |
Technology | MPPT |
Rated Power | 6600W |
Rated Voltage | 195V |
Rated Current | 120A |
Manufacturer | Felicity Solar |
Model | LBPF-M |
Technology | Lithium Ion |
Cell Voltage (V) | 3.6v |
Battery Voltage | 51.2v |
C10 Capacity | 10kWh |
Charge Voltage | 48v |
Module Catalogue # | 1 |
Number Series | Parallel | 5 in parallel |
Total C10 capacity [kWh] | 50 |
Fuse rating [A] | 250 |
Date of cell production | December 1, 2020 |
Cable cross-section [mm²] | 50 |
Module Catalogue # | 2 |
Number Series | Parallel | 5 in parallel |
Total C10 capacity [kWh] | 50 |
Fuse rating [A] | 250 |
Date of cell production | December 1, 2020 |
Cable cross-section [mm²] | 50 |
Module Catalogue # | 3 |
Number Series | Parallel | 5 in parallel |
Total C10 capacity [kWh] | 50 |
Fuse rating [A] | 250 |
Date of cell production | December 1, 2020 |
Cable cross-section [mm²] | 50 |
Module Catalogue # | 4 |
Number Series | Parallel | 6 in parallel |
Total C10 capacity [kWh] | 60 |
Fuse rating [A] | 250 |
Date of cell production | December 1, 2020 |
Cable cross-section [mm²] | 50 |
PV Generator | Expected open circuit voltage [V] |
String Number | 1 |
Value | 158.3v |
PV Generator | Measured open circuit voltage [V] |
String Number | 1 |
Value | 132,8v |
PV Generator | Expected load circuit voltage [V] |
String Number | 1 |
Value | 132.93v |
PV Generator | Measured load circuit voltage [V] |
String Number | 1 |
Value | 121.9v |
PV Generator | Expected short circuit current [A] |
String Number | 1 |
Value | 31A |
PV Generator | Measured continuity to main equipotential bar [Ohm] |
String Number | 1 |
Value | 5 |
PV Generator | Measured earth resistance of support structure [Ohm] |
String Number | 1 |
Value | 3 |
Inverter/Charge Controller | General visual inspection observations |
String Number | 1 |
Reference | All fine |
Inverter/Charge Controller | Inverter protection settings programmed to local requirements? |
String Number | 1 |
Reference | Yes |
Inverter/Charge Controller | Means of isolating the inverter been provided on the AC side? |
String Number | 1 |
Reference | Yes |
Inverter/Charge Controller | Isolating and switching devices been connected such that PC installation is wired to the “load” side and the public supply to the “source” side? |
String Number | 1 |
Reference | Yes |
Inverter/Charge Controller | All Inverters/Charge controller operating correctly? |
String Number | 1 |
Reference | Yes |
Inverter/Charge Controller | Inverter/charge controller protection settings and installer details displayed on site? |
String Number | 1 |
Reference | Yes |
Battery Storage | Wiring properly done without visual deficits |
String Number | 1 |
Reference | Yes |
Battery Storage | Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations |
String Number | 1 |
Reference | Yes |
Battery Storage | Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …) |
String Number | 1 |
Reference | Yes |
Battery Storage | Deep discharge protection, over-charge protection and temperature monitoring installed and functional |
String Number | 1 |
Reference | Yes |
General Safety/Security | Inverter protection settings programmed to local requirements? |
String Number | 1 |
Reference | Yes |
Official Letter of Request | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Request-for-NEMSA-Site-Inspection.pdf |
PV System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Single-Line-Diagram.pdf |
Charge Controller or Grid-tie Inverter | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Felicity-10kVA-Inverter-Catalogue.pdf |
Combiner Boxes | https://nemsa.gov.ng/wp-content/uploads/formidable/67/60kW-Wiring-Diagram.pdf |
Battery System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Felicity-10kWh-Battery-Catalogue-2.pdf |
Earthing & Surge Protection System | https://nemsa.gov.ng/wp-content/uploads/formidable/67/Earth-Grid-Diagram.pdf |