Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number 055
REA-NEP-MG PBG
Inspectorate Field Office closest to site location Akure
Register as Corporate
NEMSA Certificate Number CC/CEIF/PR/00609
First Name Tosin
Last Name Ibironke
Position Technical Lead
Phone 08163825313
Email i.tosin@a4tintegrated.com
Address

27b, Olumoroti Jaiyesimi Street, Gbagada, Lagos State

State Lagos
Company Name A4&T Power Solutions Limited
Company Email info@a4tintegrated.com
Company Phone 07039476932
Tax Registration Number 20022603-0001
Address

27b, Olumoroti Jaiyesimi Street, Gbagada Phase 2, Lgos

State Lagos
Name of the Village/Community Orisunbare
State Ondo
Local Government Area Ondo East
Number of Inhabitants 1250
GPS Coordinates 7.354987, 4.941713
Site Address/Detail Description

Orisunbare is a rural community in Ondo East Local Government and is located between boundary of osun and ondo state. its major occupation is cocoa farming among other farming activities. The community has a population of over 1000.

Activities Business Activity, Educational Facility, Health Care Facility, Residential
Total Solar PV Installed (kWp) 32
Total Solar PV Energy Produce Per Day (kwh) 93.6
Total Storage Capacity (kwh) 103.68
Total Load/Energy Requirement (kWh) 165.89
Storage Technology/Manufacturer Lead Acid/Eternity
Type of Coupling (AC/DC) DC
Generator Rated Power (kVA) 45
Year of Construction 2022
Fuel Type Diesel
Generator Model/Manufacturer John Deere
Operation Automatic
Date of Installation of Mini-Grid October 23, 2022
Date of Application December 5, 2022
Mini-Grid Owner (Full Name) A4&T POWER SOLUTIONS LIMITED
Phone 07039476932
Email j.ojo@a4tintegrated.com

Manufacturer Jinko
Model JKM400M-6RL3-V
Technology Monocrystalline (Half cell)
STC power (Wp) 400
Number of Cells 144
MPPT Current 88A
MPPT Voltage 1100V

Module catalogue # 10
Number Series | Parallel 8/4
Total Power (Wp) 32
Fuse (A) 250
Surge Protection Device 20KA/40KA
Converter Catalogue 0
Cable cross-section 10mm2

Manufacturer Schneider
Model CL36
Technology Conext
Rated Power 36000
Rated Voltage 1000
Rated Current 88

Manufacturer Eternity
Model 1080AH
Technology Lead Acid
Cell Voltage (V) 2.3
Battery Voltage 2V
C10 Capacity 5.37
Charge Voltage 2.43

Module Catalogue # 2
Number Series | Parallel 2/1
Total C10 capacity [kWh] 1080
Fuse rating [A] 250
Date of cell production December 5, 2022
Cable cross-section [mm²] 120

PV Generator Expected open circuit voltage [V]
String Number 1
Value 430.6
PV Generator Measured open circuit voltage [V]
String Number 1
Value 400.3
PV Generator Expected load circuit voltage [V]
String Number 1
Value 10.58
PV Generator Measured load circuit voltage [V]
String Number 1
Value 7.1
PV Generator Expected short circuit current [A]
String Number 1
Value 11.3
PV Generator Measured short circuit current [A]
String Number 1
Value 8.0
PV Generator Measured ambient temperature [°C]
String Number 1
Value 20
PV Generator Measured module temperature [°C]
String Number 1
Value 25
PV Generator Measured solar insulation [W/m²]
String Number 1
Value 912
PV Generator Alternatively, estimated insulation (cloudy, sunny, mist, …)
String Number 1
Value sunny
PV Generator Expected power output [kW]
String Number 1
Value 4000
PV Generator Measured power output [kW]
String Number 1
Value 3700
PV Generator Measured continuity to main equipotential bar [Ohm]
String Number 1
Value 0.0
PV Generator Measured earth resistance of support structure [Ohm]
String Number 1
Value 0.23
PV Generator Result of verification of measured values (OK, low, …)
String Number 1
Value ok
PV Generator General visual inspection observations
String Number 1
Value ok
PV Generator Surge Protective Devices functional (indicator at device)?
String Number 1
Value yes
PV Generator Overcurrent protection operational (correct fuse rating)?
String Number 1
Value yes
PV Generator String cables fixed and cables without damages
String Number 1
Value yes

Inverter/Charge Controller General visual inspection observations
String Number 1
Reference ok
Inverter/Charge Controller Inverter protection settings programmed to local requirements?
String Number 1
Reference yes
Inverter/Charge Controller When an RCD is installed to the AC circuit feeding an inverter, the RCD type shall be verified to ensure it has been selected according to the requirements of IEC 60364
String Number 1
Reference yes
Inverter/Charge Controller Means of isolating the inverter been provided on the AC side?
String Number 1
Reference yes
Inverter/Charge Controller Isolating and switching devices been connected such that PC installation is wired to the “load” side and the public supply to the “source” side?
String Number 1
Reference yes
Inverter/Charge Controller All Inverters/Charge controller operating correctly?
String Number 1
Reference yes
Inverter/Charge Controller Inverter/charge controller protection settings and installer details displayed on site?
String Number 1
Reference yes

Battery Storage General visual inspection observations
String Number 2
Reference ok
Battery Storage Wiring properly done without visual deficits
String Number 2
Reference yes
Battery Storage Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations
String Number 2
Reference yes
Battery Storage Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …)
String Number 2
Reference yes
Battery Storage State of charge (If applicable state of health)
String Number 2
Reference NA
Battery Storage Safety measures for the respective types of batteries applied
String Number 2
Reference yes
Battery Storage Deep discharge protection, over-charge protection and temperature monitoring installed and functional
String Number 2
Reference yes
Battery Storage Number of full cycles calculated by the monitoring system (if applicable)
String Number 2
Reference NA
Battery Storage Cell voltage
String Number 2
Reference 2.41
Battery Storage Cell temperature
String Number 2
Reference 28.2

General Safety/Security General visual inspection observations
String Number 1
Reference OK
General Safety/Security Inverter protection settings programmed to local requirements?
String Number 1
Reference Yes
General Safety/Security Means of isolating the inverter been provided on the AC side?
String Number 1
Reference yes
General Safety/Security Isolating and switching devices been connected such that PC installation is wired to the “load” side and the public supply to the “source” side?
String Number 1
Reference Yes
General Safety/Security All Inverters/Charge controller operating correctly?
String Number 1
Reference yes
General Safety/Security Inverter/charge controller protection settings and installer details displayed on site?
String Number 1
Reference yes
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/Letter-for-Claims-Orisunbare.pdf
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/SLD-PV-SYSTEM-PANEL-DATASHEET.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/SLD_Inverter-System-1.pdf
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/COMBINER-BOX.pdf
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/BATTERY-SYSTEM-CONFIGURATION.docx.pdf
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Earthing-System-Surge-Protection.docx.pdf
User ID Joseph Ojo