Admin Request for Inspection REA Solar Mini Grid

Application for REA Solar Mini-Grid Project
REA Code REA-NEP-MG
REA LOT Number rea-nep/mg/pbg/89/20
REA-NEP-MG PBG
Inspectorate Field Office closest to site location Uyo
Register as Corporate
NEMSA Certificate Number CC/CEIF/PR/03490
First Name Chris
Last Name Ebiware
Position Country Manager
Phone 08039253885
Email cebiware@renewvia.com
Address

11 Chikwele Street, Unity Estate, Eliogboilo, Port Harcourt, Rivers State, Nigeria.

State Rivers
Company Name Renewvia Soalr Nigeria Limited
Company Email info@renewvia.com
Company Phone 08039253885
Tax Registration Number 19844167-0001
Address

11 Chikwele Street, Unity Estate, Eliogboilo, Port Harcourt, Rivers State, Nigeria.

State Rivers
Name of the Village/Community Emereoke
State Akwa Ibom
Local Government Area Eastern Obolo
Number of Inhabitants 2600
GPS Coordinates 4.5025801, 7.67457
Activities Business Activity, Administrative Facility, Educational Facility, Health Care Facility, Residential
Total Solar PV Installed (kWp) 28.08
Total Solar PV Energy Produce Per Day (kwh) 85.54
Total Storage Capacity (kwh) 66.6
Total Load/Energy Requirement (kWh) 86.42
Storage Technology/Manufacturer Lithium Iron Phosphate
Type of Coupling (AC/DC) DC
Generator Rated Power (kVA) 62.5
Year of Construction 2021
Fuel Type Diesel
Generator Model/Manufacturer Electromak
Operation 180
Date of Installation of Mini-Grid April 1, 2022
Date of Application September 25, 2022
Mini-Grid Owner (Full Name) Chris Ebiware
Phone 08039253885
Email cebiware@renewvia.com

Manufacturer Jinko Solar
Model JKM390M-72
Technology Monocrystalline
STC power (Wp) 390
Number of Cells 72
MPPT Current 9.49
MPPT Voltage 41.1

Module catalogue # 1
Number Series | Parallel 4|3
Total Power (Wp) 4680
Fuse (A) 50
Surge Protection Device 40KA
Converter Catalogue 1
Cable cross-section 10MMSQ
Module catalogue # 2
Number Series | Parallel 4|3
Total Power (Wp) 4680
Fuse (A) 50
Surge Protection Device 40KA
Converter Catalogue 2
Cable cross-section 10MMSQ
Module catalogue # 3
Number Series | Parallel 4|3
Total Power (Wp) 4680
Fuse (A) 50
Surge Protection Device 40KA
Converter Catalogue 3
Cable cross-section 10MMSQ
Module catalogue # 4
Number Series | Parallel 4|3
Total Power (Wp) 4680
Fuse (A) 50
Surge Protection Device 40KA
Converter Catalogue 4
Cable cross-section 10MMSQ
Module catalogue # 5
Number Series | Parallel 4|3
Total Power (Wp) 4680
Fuse (A) 50
Surge Protection Device 40KA
Converter Catalogue 5
Cable cross-section 10MMSQ
Module catalogue # 6
Number Series | Parallel 4|3
Total Power (Wp) 4680
Fuse (A) 50
Surge Protection Device 40KA
Converter Catalogue 6
Cable cross-section 10MMSQ

Manufacturer Victron
Model Smart Solar 250/85
Technology MPPT
Rated Power 4900
Rated Voltage 250
Rated Current 85
Manufacturer Victron
Model Smart Solar 250/85
Technology MPPT
Rated Power 4900
Rated Voltage 250
Rated Current 85
Manufacturer Victron
Model Smart Solar 250/85
Technology MPPT
Rated Power 4900
Rated Voltage 250
Rated Current 85
Manufacturer Victron
Model Smart Solar 250/85
Technology MPPT
Rated Power 4900
Rated Voltage 250
Rated Current 85
Manufacturer Victron
Model Smart Solar 250/85
Technology MPPT
Rated Power 4900
Rated Voltage 250
Rated Current 85
Manufacturer Victron
Model Smart Solar 250/85
Technology MPPT
Rated Power 4900
Rated Voltage 250
Rated Current 85

Manufacturer Solar MD
Model SS202-01
Technology Lithium Iron Phosphate
Cell Voltage (V) 3.2
Battery Voltage 51.2
C10 Capacity 245
Charge Voltage 53.4

PV Generator Expected open circuit voltage [V]
String Number 6
Value 194.4
PV Generator Measured open circuit voltage [V]
String Number 6
Value 186.6
PV Generator Expected load circuit voltage [V]
String Number 6
Value 158.56
PV Generator Measured load circuit voltage [V]
String Number 6
Value 148.25
PV Generator Expected short circuit current [A]
String Number 6
Value 31.38
PV Generator Measured ambient temperature [°C]
String Number 6
Value 37
PV Generator Alternatively, estimated insulation (cloudy, sunny, mist, …)
String Number 6
Value sunny
PV Generator Expected power output [kW]
String Number 6
Value 4.68
PV Generator Measured insulation resistance [Mega Ohm]
String Number 6
Value 1000
PV Generator Measured earth resistance of support structure [Ohm]
String Number 6
Value 7.2
PV Generator General visual inspection observations
String Number 6
Value OK
PV Generator Surge Protective Devices functional (indicator at device)?
String Number 6
Value OK
PV Generator Overcurrent protection operational (correct fuse rating)?
String Number 6
Value YES
PV Generator String cables fixed and cables without damages
String Number 6
Value YES
PV Generator Connectors properly connected under no mechanical strain
String Number 6
Value YES

Inverter/Charge Controller General visual inspection observations
String Number 6
Reference OK
Inverter/Charge Controller Inverter protection settings programmed to local requirements?
String Number 6
Reference YES
Inverter/Charge Controller Means of isolating the inverter been provided on the AC side?
String Number 6
Reference YES
Inverter/Charge Controller Isolating and switching devices been connected such that PC installation is wired to the “load” side and the public supply to the “source” side?
String Number 6
Reference YES
Inverter/Charge Controller All Inverters/Charge controller operating correctly?
String Number 6
Reference YES

Battery Storage General visual inspection observations
String Number 1
Reference OK
Battery Storage Wiring properly done without visual deficits
String Number 1
Reference YES
Battery Storage Tightening torque of all screws to connectors to the batteries and in between the cells of the batteries is according to the equipment manufacturer’s recommendations
String Number 1
Reference YES
Battery Storage Battery inverter or charge controller parameters are properly set (correct system configuration, date and time, control of the load shedding relays, reading of external temperature sensor verified, …)
String Number 1
Reference YES
Battery Storage State of charge (If applicable state of health)
String Number 1
Reference 100%
Battery Storage Deep discharge protection, over-charge protection and temperature monitoring installed and functional
String Number 1
Reference YES

General Safety/Security General visual inspection observations
Official Letter of Request https://nemsa.gov.ng/wp-content/uploads/formidable/67/220422-Request-for-NEMSA-Site-Inspection-at-Emereoke-1-150×150.jpg
PV System https://nemsa.gov.ng/wp-content/uploads/formidable/67/Emereoke-Electrical-Wiring-Diagram-Final_SLD.pdf
Charge Controller or Grid-tie Inverter https://nemsa.gov.ng/wp-content/uploads/formidable/67/EMEREOKE-NEMSA-APPLICATION-03-150×150.jpg
Combiner Boxes https://nemsa.gov.ng/wp-content/uploads/formidable/67/EMEREOKE-NEMSA-APPLICATION-03-1-150×150.jpg
Battery System https://nemsa.gov.ng/wp-content/uploads/formidable/67/EMEREOKE-NEMSA-APPLICATION-07-150×150.jpg
Earthing & Surge Protection System https://nemsa.gov.ng/wp-content/uploads/formidable/67/EMEREOKE-NEMSA-APPLICATION-16-150×150.jpg